Introduction to Switchgear
Switchgear
The apparatus used for switching, controlling and protecting
the electrical circuits and equipment is known as switchgear. The switchgear
equipment is essentially concerned with switching and interrupting currents
either under normal or abnormal operating conditions. The tumbler switch with ordinary fuse is the
simplest form of switchgear and is used to control and protect lights and other
equipment in homes, offices, etc. For circuits
of a higher rating, a high-rupturing capacity (H.R.C.) fuse in conjunction with a
switch may serve the purpose of controlling and protecting the circuit. However, such switchgear cannot be used
profitably on a high voltage system (3·3 kV) for two reasons.
Firstly, when a fuse blows, it takes some time to replace it and consequently, there is an interruption of service to the customers.
Secondly, the fuse cannot successfully interrupt large fault currents that result from the faults on the high voltage system.
With the advancement of the power system, lines and other equipment operate at high voltages and carry large currents. When a short circuit occurs on the system, the heavy current flowing through the equipment may cause considerable damage. In order to interrupt such heavy fault currents, automatic circuit breakers (or simply circuit breakers) are used. A circuit breaker is switchgear which can open or close an electrical circuit under both normal and abnormal conditions. Even in instances where a fuse is adequate, as regards to breaking capacity, a circuit breaker may be preferable. It is because a circuit breaker can close circuits, as well as break them without replacement and thus has a wider range of use altogether than a fuse.Essential Features of Switchgear
The essential features of switchgear are :
(i) Complete reliability. With the continued trend of interconnection and the increasing capacity of generating stations, the need for reliable switchgear has become of paramount importance. This is not surprising because switchgear is added to the power system to improve reliability. When the fault occurs on any part of the power system, the switchgear must operate to isolate the faulty section from the remaining circuit.
(ii) Absolutely certain discrimination. When the fault occurs on any section of the power system, the switchgear must be able to discriminate between the faulty section and the healthy section. It should isolate the faulty section from the system without affecting the healthy section. This will ensure the continuity of supply.
(iii) Quick operation. When the fault occurs on any part of the power system, the switchgear must operate quickly so that no damage is done to generators, transformers and other equipment by the short-circuit currents. If the fault is not cleared by switchgear quickly, it is likely to spread into healthy parts, thus endangering complete shut down of the system.
(iv) Provision for manual control. Switchgear must have provision for manual control. In case the electrical (or electronics) control fails, the necessary operation can be carried out through manual control. (v) Provision for instruments. There must be a provision for instruments that may be required. These may be in the form of ammeter or voltmeter on the unit itself or the necessary current and voltage transformers for connecting to the main switchboard or a separate instrument panel.
Switchgear Equipment
Switchgear covers a wide range of equipment concerned with
switching and interrupting currents under both normal and abnormal
conditions. It includes switches, fuses,
circuit breakers, relays, and other equipment.
A brief account of these devices is given below. However, the reader may find a detailed
discussion on them in the subsequent chapters.
1. Switches. A switch is a device that is used to open or close an electrical circuit in a convenient way. It can be used under full-load or no-load conditions but it cannot interrupt the fault currents. When the contacts of a switch are opened, an *arc is produced in the air between the contacts. This is particularly true for circuits of high voltage and large current capacity.
The switches may be classified into
(i) Air-break switch. It is an air switch and is designed to open a circuit under load. In order to quench the arc that occurs on opening such a switch, special arcing horns are provided. Arcing horns are pieces of metals between which arc is formed during the opening operation. As the switch opens, these horns are spread farther and farther apart. Consequently, the arc is lengthened, cooled and interrupted. Air-break switches are generally used outdoor for circuits of medium capacity such as lines supplying an industrial load from a main transmission line or feeder.
(ii) Isolator or disconnecting switch. It is essentially a knife switch and is designed to open a circuit under no load. Its main purpose is to isolate one portion of the circuit from the other and is not intended to be opened while current is flowing in the line. Such switches are generally used on both sides of circuit breakers in order that repairs and replacement of circuit breakers can be made without any danger. They should never be opened until the circuit breaker in the same circuit has been opened and should always be closed before the circuit breaker is closed.
(iii) Oil switches. As the name implies, the contacts of such switches are opened under oil, usually transformer oil. The effect of oil is to cool and quench the arc that tends to form when the circuit is opened. These switches are used for circuits of high voltage and large current-carrying capacities.
2. Fuses. A fuse is a short piece of wire or thin strip which melts when excessive current flows through it for sufficient time. It is inserted in series with the circuit to be protected. Under normal operating conditions, the fuse element it at a temperature below its melting point. Therefore, it carries the normal load current without overheating. However, when a short circuit or overload occurs, the current through the fuse element increases beyond its rated capacity. This raises the temperature and the fuse element melts (or blows out), disconnecting the circuit protected by it. In this way, a fuse protects the machines and equipment from damage due to excessive currents. It is worthwhile to note that a fuse performs both detection and interruption functions.
3. Circuit breakers. A circuit breaker is an equipment which can open or close a circuit under all conditions viz. no-load, full load and fault conditions. It is so designed that it can be operated manually (or by remote control) under normal conditions and automatically under fault conditions. For the latter operation, a relay circuit is used with a circuit breaker. Fig. 16.1 (i) shows the parts of a typical oil circuit breaker whereas Fig. 16.1 (ii) shows its control by a relay circuit. The circuit breaker essentially consists of moving and fixed contacts enclosed in a strong metal tank and immersed in oil, known as transformer oil. Under normal operating conditions, the contacts remain closed and the circuit breaker carries the full-load current continuously. In this condition, the e.m.f. in the secondary winding of the current transformer (C.T.) is insufficient to operate the trip coil of the breaker but the contacts can be opened (and hence the circuit can be opened) by manual or remote control. When a fault occurs, the resulting overcurrent in the C.T. primary winding increases the secondary e.m.f. This energizes the trip coil of the breaker and moving contacts are pulled down, thus opening the contacts and hence the circuit. The arc produced during the opening operation is quenched by the oil. It is interesting to note that relay performs the function of detecting a fault whereas the circuit breaker does the actual circuit interruption.
4. Relays. A relay is a device that detects the fault and supplies information to the breaker for circuit interruption. It can be divided into three parts viz. (i) The primary winding of a *current transformer (C.T.) is connected in series with the circuit to be protected. The primary winding often consists of the main conductor itself. (ii) The second circuit is the secondary winding of C.T. connected to the relay operating coil. (iii) The third circuit is the tripping circuit which consists of a source of supply, the trip coil of the circuit breaker and the relay stationary contacts. Under normal load conditions, the e.m.f. of the secondary winding of C.T. is small and the current flowing in the relay operating coil is insufficient to close the relay contacts. This keeps the trip coil of the circuit breaker unenergised. Consequently, the contacts of the circuit breaker remain closed and it carries the normal load current. When a fault occurs, a large current flows through the relay operating coil. The relay contacts are closed and the trip coil of the circuit breaker is energized to open the contacts of the circuit breaker.
Bus-Bar Arrangements
When a number of generators or feeders operating at the same
voltage have to be directly connected electrically, bus-bars are used as the
common electrical component. *Bus-bars
are copper rods or thin-walled tubes and operate at a constant voltage. We shall discuss some important bus-bars
arrangements used for power stations and sub-stations. All the diagrams refer to the 3-phase arrangement
but are shown in single-phase for simplicity.
(1) Single Bus-bar System. The single busbar system has the simplest design and is used for power stations. It is also used in small outdoor stations having relatively few outgoing or incoming feeders and lines. Fig. shows the single bus-bar system for a typical power station. The generators, outgoing lines, and transformers are connected to the bus-bar. Each generator and feeder is controlled by a circuit breaker. The isolators permit to isolate generators, feeders and circuit breakers from the bus-bar for maintenance.
The chief advantages of this type of arrangement are low initial cost, less maintenance, and simple operation.
Disadvantages. The single bus-bar system has the following three principal disadvantages :
(i) The bus-bar cannot be cleaned, repaired or tested without de-energizing the whole system.
(ii) If a fault occurs on the bus-bar itself, there is a complete interruption of supply.
(iii) Any fault on the system is fed by all the generating capacity, resulting in very large fault currents.
(2) The single bus-bar system with Sectionalisation. In large generating stations where several units are installed, it is a common practice to sectionalize the bus so that fault on any section of the bus-bar will not cause a complete shutdown. This is illustrated in Fig. which shows the bus-bar divided into two sections connected by a circuit breaker and isolators.
Three principal advantages are claimed for this arrangement.
Firstly, if a fault occurs on any section of the bus-bar, that section can be isolated without affecting the supply to other sections.
Secondly, if a fault occurs on any feeder, the fault current is much **lower than with a sectionalize bus-bar. This permits the use of circuit breakers of lower capacity in the feeders.
Thirdly, repairs and maintenance of any section of the bus-bar can be carried out by de-energizing that section only, eliminating the possibility of complete shut-down. It is worthwhile to keep in mind that a circuit breaker should be used as the sectionalizing switch so that the uncoupling of the bus-bars may be carried out safely during load transfer. Moreover, the circuit breaker itself should be provided with isolators on both sides so that its maintenance can be done while the bus-bars are alive.
(3) Duplicate bus-bar system. In large stations, it is important that breakdowns and maintenance should interfere as little as possible with continuity of supply. In order to achieve this objective, the duplicate bus-bar system is used in important stations. Such a system consists of two bus-bars, a “main bus-bar’’ and a “spare” bus-bar (see Fig. ). Each generator and feeder may be connected to either bus-bar with the help of bus coupler which consists of a circuit breaker and isolators. In the scheme shown in Fig., service is interrupted during the switch over from one bus to another. However, if it were desired to switch a circuit from one to another without interruption of service, there would have to be two circuit breakers per circuit. Such an arrangement will be too expensive.
Advantages
(i) If repair and maintenance are to be carried on the main bus, the supply need not be interrupted as the entire load can be transferred to the spare bus.
(ii) The testing of feeder circuit breakers can be done by putting them on spare bus-bar, thus keeping the main bus-bar undisturbed.
(iii) If a fault occurs on the bus-bar, the continuity of supply to the circuit can be maintained by transferring it to the other bus-bar.
Switchgear Accommodation
The main components of switchgear are circuit breakers,
switches, bus-bars, instruments and instrument transformers. It is necessary to house the switchgear in
power stations and sub-stations in such a way so as to safeguard personnel
during operation and maintenance and to ensure that the effects of fault on any
section of the gear is confined to a limited region.
Depending upon the
voltage to be handled, switchgear may be broadly classified into
(i) Outdoor type. For voltages beyond 66 kV, switchgear equipment is installed outdoor. It is because, for such voltages, the clearances between conductors and the space required for switches, circuit breakers, transformers, and other equipment become so great that it is not economical to install all such equipment indoor.
(ii) Indoor type. For voltages below 66 kV, switchgear is generally installed indoor because of economic considerations. The indoor switchgear is generally of metal-clad type. In this type of construction, all live parts are completely enclosed in an earthed metal casing. The primary object of this practice is the definite localization and restriction of any fault to its place of origin.
Short-Circuit
Whenever a fault occurs on a network such that a large
current flows in one or more phases, a short circuit is said to have occurred.
When a short circuit occurs, a heavy current called short circuit current flows
through the circuit. This can be beautifully illustrated by referring to Fig.
16.6 where a single-phase generator of voltage V and internal impedance Zi is
supplying to a load Z. Under normal conditions,
the current in the circuit is limited by load impedance Z. However, if the load terminals get shorted
due to any reason, the circuit impedance is reduced to a very low value; being
Zi in this case. As Zi is very small,
therefore, a large current flows through the circuit. This is called a short-circuit current. It is worthwhile to make a distinction between a short-circuit and overload. When a short-circuit occurs,
the voltage at the fault point is reduced to zero and the current of abnormally high
magnitude flows through the network to the point of fault. On the other hand, an overload means that
loads greater than the designed values have been imposed on the system. Under such conditions, the voltage at the
overload point may be low, but not zero.
The Undervoltage conditions may extend for some distance beyond the
overload point into the remainder of the system. The currents in the overloaded equipment are
high but are substantially lower than that in the case of a short-circuit.
Causes of short-circuiting.
A short circuit in the power system is the result of some kind of abnormal conditions in the system. It may be caused due to internal and/or external effects.(i) Internal effects are caused by the breakdown of equipment or transmission lines, from deterioration of insulation in a generator, transformer, etc. Such troubles may be due to the aging of insulation, inadequate design or improper installation.
(ii) External effects causing short circuits include insulation failure due to lightning surges, overloading of equipment causing excessive heating; mechanical damage by the public, etc.
Effects of short-circuiting.
When a short-circuit occurs, the current in the system increases to an abnormally high value while the system voltage decreases to a low value.
(i) The heavy current is due to short-circuit causes excessive heating which may result in fire or explosion. Sometimes short-circuit takes the form of an arc and causes considerable damage to the system. For example, an arc on a transmission line not cleared quickly will burn the conductor severely causing it to break, resulting in a long time interruption of the line.
(ii) The low voltage created by the fault has a very harmful effect on the service rendered by the power system. If the voltage remains low for even a few seconds, the consumers’ motors may be shut down and generators on the power system may become unstable.
Due to the above detrimental effects of short-circuit, it is desirable and necessary to disconnect the faulty section and restore normal voltage and current conditions as quickly as possible.
Short-Circuit Currents
Most of the failures on the power system lead to a short-circuit fault and cause heavy current to flow in the system. The calculations of these short-circuit
currents are important for the following reasons :
(i) A short-circuit on the power system is cleared by a circuit breaker or a fuse. It is necessary, therefore, to know the maximum possible values of short-circuit current so that the switchgear of suitable rating may be installed to interrupt them.
(ii) The magnitude of short-circuit current determines the setting and sometimes the types and location of the protective system.
(iii) The magnitude of short-circuit current determines the size of the protective reactors which must be inserted in the system so that the circuit breaker is able to withstand the fault current.
(iv) The calculation of short-circuit currents enables us to make the proper selection of the associated apparatus (e.g. bus-bars, current transformers, etc.) so that they can withstand the forces that arise due to the occurrence of short circuits.
Faults in a Power System
A fault occurs when two or more conductors that normally
operate with a potential difference come in contact with each other. These faults may be caused by the sudden failure
of a piece of equipment, accidental damage or short-circuit to overhead lines
or insulation failure resulting from lightning surges. Irrespective of the causes, the faults in a 3-phase system can be classified into two main categories viz. (i) Symmetrical
faults (ii) Unsymmetrical faults
(i) Symmetrical faults. That fault which gives rise to symmetrical fault currents (i.e. equal faults currents with 120-degree displacement) is called an asymmetrical fault. The most common example of symmetrical fault is when all the three conductors of a 3-phase line are brought together simultaneously into a short-circuit condition.
(ii) Unsymmetrical faults. Those faults which give rise to unsymmetrical currents (i.e. unequal line currents with unequal displacement) are called unsymmetrical faults.
The unsymmetrical faults may take one of the following forms : (a)
Single line-to-ground fault (b)
Line-to-line fault (c) Double
line-to-ground fault The great majority of faults on the power system are of
unsymmetrical nature; the most common type being a short-circuit from one line
to ground. The calculations of such
fault currents are made by “symmetrical components” method
Really thanks for sharing this useful post .Got very good information about Switchgear.
ReplyDeleteSwitchgear NZ
I was just browsing through the internet looking for some information and came across your blog. I am impressed by the information that you have on this blog. It shows how well you understand this subject. Bookmarked this page, will come back for more. electric vehicle charging stations
ReplyDeleteThanks for sharing the amazing content. I will also share with my friends. Great content thanks a lot.Visit What is a switchgear ? Definition, Types & Features!
ReplyDeleteA great website with interesting and unique material what else would you need. MJ Movers
ReplyDeleteInteresting post. I Have Been wondering about this issue, so thanks for posting. Pretty cool post.It 's really very nice and Useful post.Thanks blood pressure 911 tablets
ReplyDeleteThanks for sharing good information Visit Here :
ReplyDeletemodular electric switch board
Hi, This article is genuinely pleasant and I have learned lot of things from it on the topic of Electrical Switchgear. thanks.
ReplyDelete